Inductive sensor NJ2-8GM-N-Y33681
Part number: NJ2-8GM-N-Y33681
Specification
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Rated operating distance | 2 mm | |
Installation | non-flush | |
Assured operating distance | 0 ... 1.62 mm | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.3 | |
Reduction factor r304 | 0.85 | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8 V | |
Switching frequency | 0 ... 5000 Hz | |
Hysteresis | 1 ... 10 typ. 5 % | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | ≤ 1 mA | |
Functional safety related parameters | ||
MTTFd | 5887 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 0.5 m | |
Core cross section | 0.14 mm2 | |
Housing material | Stainless steel 1.4305 / AISI 303 | |
Sensing face | PBT | |
Degree of protection | IP67 | |
ECLASS 13.0 | 27274001 | |
ECLASS 12.0 | 27274001 | |
ECLASS 11.0 | 27270101 | |
ECLASS 10.0.1 | 27270101 | |
ECLASS 9.0 | 27270101 | |
ECLASS 8.0 | 27270101 | |
ECLASS 5.1 | 27270101 | |
ETIM 9.0 | EC002714 | |
ETIM 8.0 | EC002714 | |
ETIM 7.0 | EC002714 | |
ETIM 6.0 | EC002714 | |
ETIM 5.0 | EC002714 | |
UNSPSC 12.1 | 39121550 |