Inductive sensor NBB3-V3-Z4-3G-3D

Part number: NBB3-V3-Z4-3G-3D

  • 3 mm flush
  • 2-wire DC
  • 60 V DC output
  • ATEX-/IECEx-approvals for zone 2/22 (Ex ec/tc)
  • Specification

    General specifications
    Switching functionNormally open (NO)
    Output typeTwo-wire
    Rated operating distance3 mm
    Installationflush
    Output polarityDC
    Assured operating distance0 ... 2.4 mm
    Actual operating distance2.7 ... 3.3 mm typ.
    Reduction factor rAl 0.45
    Reduction factor rCu 0.35
    Reduction factor r304 0.8
    Reduction factor rBrass 0.5
    Output type2-wire
    Nominal ratings
    Operating voltage5 ... 60 V DC
    Switching frequency0 ... 2000 Hz
    Hysteresistyp. 0.2 mm
    Reverse polarity protectionreverse polarity protected
    Short-circuit protectionno
    Inductive overvoltage protectionyes
    Voltage drop≤ 4 V
    Voltage drop at IL
    Voltage drop IL = 10 mA, switching element on3.4 ... 3.9 V typ. 3.6 V
    Operating current4 ... 100 mA
    Lowest operating current4 mA
    Off-state current0.4 ... 0.55 mA typ. 0.46 mA
    Time delay before availability≤ 1 ms
    Switching state indicatorLED, yellow
    Limit data
    Tightening torque, fastening screws0.4 Nm
    Functional safety related parameters
    MTTFd1552 a
    Mission Time (TM)20 a
    Diagnostic Coverage (DC)0 %
    Compliance with standards and directives
    Standard conformity
    StandardsEN 60947-5-2:2007
    EN 60947-5-2/A1:2012
    IEC 60947-5-2:2007
    IEC 60947-5-2 AMD 1:2012
    Approvals and certificates
    IECEx approval
    Equipment protection level Gc (ec)IECEx TUR 21.0019X
    Equipment protection level Dc (tc)IECEx TUR 21.0020X
    ATEX approval
    Equipment protection level Gc (ec)TÜV 20 ATEX 8525 X
    Equipment protection level Dc (tc)TÜV 20 ATEX 8526 X
    UL approvalcULus Listed, General Purpose
    Ambient conditions
    Ambient temperature-25 ... 85 °C (-13 ... 185 °F)
    Mechanical specifications
    Connection typecable PVC , 130 mm
    Core cross section0.14 mm2
    Housing materialPBT
    Sensing facePBT
    Degree of protectionIP67
    Cable
    Bending radius> 10 x cable diameter
    General information
    Use in the hazardous areasee instruction manuals
    ECLASS 13.027274001
    ECLASS 12.027274001
    ECLASS 11.027270101
    ECLASS 10.0.127270101
    ECLASS 9.027270101
    ECLASS 8.027270101
    ECLASS 5.127270101
    ETIM 9.0EC002714
    ETIM 8.0EC002714
    ETIM 7.0EC002714
    ETIM 6.0EC002714
    ETIM 5.0EC002714
    UNSPSC 12.139121550