Inductive sensor NJ40-FP-SN-P4

Part number: NJ40-FP-SN-P4

  • 40 mm non-flush
  • Specification

    General specifications
    Switching functionNormally closed (NC)
    Output typeNAMUR with safety function
    Rated operating distance40 mm
    Installationnon-flush
    Assured operating distance0 ... 32.4 mm
    Reduction factor rAl 0.4
    Reduction factor rCu 0.3
    Reduction factor r304 0.85
    Output type2-wire
    Nominal ratings
    Nominal voltage8.2 V (Ri approx. 1 kΩ)
    Switching frequency0 ... 100 Hz
    Current consumption
    Measuring plate not detectedmin. 3 mA
    Measuring plate detected≤ 1 mA
    Functional safety related parameters
    MTTFd7560 a
    Mission Time (TM)20 a
    Diagnostic Coverage (DC)0 %
    Compliance with standards and directives
    Standard conformity
    NAMUREN 60947-5-6:2000
    IEC 60947-5-6:1999
    StandardsEN 60947-5-2:2007
    EN 60947-5-2/A1:2012
    IEC 60947-5-2:2007
    IEC 60947-5-2 AMD 1:2012
    Approvals and certificates
    IECEx approval
    Equipment protection level GbIECEx PTB 11.0092X
    Equipment protection level DaIECEx PTB 11.0092X
    ATEX approval
    Equipment protection level GbPTB 00 ATEX 2049 X
    Equipment protection level DaPTB 00 ATEX 2049 X
    UL approvalcULus Listed, General Purpose
    KCC approval
    Hazardous Location18-AV4BO-0478X
    Ambient conditions
    Ambient temperature-40 ... 100 °C (-40 ... 212 °F)
    Mechanical specifications
    Connection type1/2 NPT terminal compartment, wire cross-section ≤ 2.5 mm2
    Core cross sectionup to 2.5 mm2
    Housing materialPBT/metal
    Sensing facePBT
    Degree of protectionIP68
    General information
    Use in the hazardous areasee instruction manuals
    ECLASS 13.027274101
    ECLASS 12.027274101
    ECLASS 11.027272401
    ECLASS 10.0.127272401
    ECLASS 9.027272401
    ECLASS 8.027272401
    ECLASS 5.127272401
    ETIM 9.0EC002714
    ETIM 8.0EC002714
    ETIM 7.0EC002714
    ETIM 6.0EC002714
    ETIM 5.0EC002714
    UNSPSC 12.139121550