Specification
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Rated operating distance | 6 mm | |
Installation | flush | |
Assured operating distance | 0 ... 4.8 mm | |
Actual operating distance | 5.4 ... 6.6 mm typ. | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.3 | |
Reduction factor r304 | 0.7 | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
Switching frequency | 0 ... 5000 Hz | |
Hysteresis | 0 ... 0.3 typ. 0.1 % | |
Reverse polarity protection | reverse polarity protected | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | ≤ 1 mA | |
Functional safety related parameters | ||
MTTFd | 4540 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 | |
Approvals and certificates | ||
IECEx approval | ||
Equipment protection level Gb | IECEx PTB 11.0021X | |
Equipment protection level Da | IECEx PTB 11.0021X | |
Equipment protection level Mb | IECEx PTB 11.0021X | |
ATEX approval | ||
Equipment protection level Gb | PTB 00 ATEX 2032 X | |
Equipment protection level Da | PTB 00 ATEX 2032 X | |
UL approval | cULus Listed, General Purpose | |
CCC approval | ||
Hazardous Location | 2020322315002302 | |
NEPSI approval | ||
NEPSI certificate | GYJ16.1394X | |
CML approval | on request | |
ANZEx | 19.3001X | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Storage temperature | -40 ... 100 °C (-40 ... 212 °F) | |
Mechanical specifications | ||
Connection type | cable | |
Housing material | PBT | |
Sensing face | PBT | |
Degree of protection | IP67 | |
Cable | ||
Cable diameter | 4.8 mm ± 0.2 mm | |
Bending radius | > 10 x cable diameter | |
Material | PUR | |
Core cross section | 0.34 mm2 | |
Length | 2 m | |
Mass | 78 g | |
General information | ||
Use in the hazardous area | see instruction manuals | |
ECLASS 13.0 | 27274001 | |
ECLASS 12.0 | 27274001 | |
ECLASS 11.0 | 27270101 | |
ECLASS 10.0.1 | 27270101 | |
ECLASS 9.0 | 27270101 | |
ECLASS 8.0 | 27270101 | |
ECLASS 5.1 | 27270101 | |
ETIM 9.0 | EC002714 | |
ETIM 8.0 | EC002714 | |
ETIM 7.0 | EC002714 | |
ETIM 6.0 | EC002714 | |
ETIM 5.0 | EC002714 | |
UNSPSC 12.1 | 39121550 |