Inductive sensor NJ40-FP-SN-P1
Part number: NJ40-FP-SN-P1
Specification
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR with safety function | |
Rated operating distance | 40 mm | |
Installation | non-flush | |
Assured operating distance | 0 ... 32.4 mm | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.3 | |
Reduction factor r304 | 0.85 | |
Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation. | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
Switching frequency | 0 ... 100 Hz | |
Current consumption | ||
Measuring plate not detected | ≥ 3 mA | |
Measuring plate detected | ≤ 1 mA | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
MTTFd | 7560 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 | |
Approvals and certificates | ||
IECEx approval | ||
Equipment protection level Gb | IECEx PTB 11.0092X | |
Equipment protection level Da | IECEx PTB 11.0092X | |
Equipment protection level Mb | IECEx PTB 11.0092X | |
ATEX approval | ||
Equipment protection level Gb | PTB 00 ATEX 2049 X | |
Equipment protection level Da | PTB 00 ATEX 2049 X | |
UL approval | cULus Listed, General Purpose | |
CCC approval | ||
Hazardous Location | 2020322315002308 | |
NEPSI approval | ||
NEPSI certificate | GYJ16.1392X | |
KCC approval | ||
Hazardous Location | 18-AV4BO-0478X | |
Ambient conditions | ||
Ambient temperature | -40 ... 100 °C (-40 ... 212 °F) | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross section | up to 2.5 mm2 , stripped insulation length: 7 mm | |
Connection (system side) | screw terminals , M20 x 1.5 cable gland , usable thread length 10 mm , screw-in depth max. 10 mm | |
Housing material | PBT | |
Sensing face | PBT | |
Degree of protection | IP68 | |
General information | ||
Use in the hazardous area | see instruction manuals | |
ECLASS 13.0 | 27274101 | |
ECLASS 12.0 | 27274101 | |
ECLASS 11.0 | 27272401 | |
ECLASS 10.0.1 | 27272401 | |
ECLASS 9.0 | 27272401 | |
ECLASS 8.0 | 27272401 | |
ECLASS 5.1 | 27272401 | |
ETIM 9.0 | EC002714 | |
ETIM 8.0 | EC002714 | |
ETIM 7.0 | EC002714 | |
ETIM 6.0 | EC002714 | |
ETIM 5.0 | EC002714 | |
UNSPSC 12.1 | 39121550 |