TeSys LRD thermal overload relay by Schneider

Part number: LRD332L

  • differential device with phase failure (loss)
  • connection by EverLink BTR screw terminals 
  • mounting on DIN rail or screw fixing
  • Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, RoHs/Reach)
  • Successor is:

Specification

Product or component typeDifferential thermal overload relay
Relay applicationMotor protection
Product compatibilityLC1D40A, LC1D50A, LC1D65A
Network typeAC/DC
Thermal overload classClass 20 conforming to IEC 60947-4-1
Thermal protection adjustment range23…32 A
Network frequency0...400 Hz
[Ui] rated insulation voltagePower circuit: 690 V conforming to IEC 60947-4-1
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV
Temperature compensation-20…60 °C